Abstract

In cold-climate locations, where natural gas is burned during the day to enrich greenhouses with carbon dioxide, water tanks (buffers) are often used to store the surplus daytime heat for nighttime heating. A practical control strategy for filling (charging) and emptying (discharging) of the buffer, based on a virtual value (costate) of the stored heat (the state), is suggested and illustrated by simulation. Heating and ventilation decisions are obtained by maximizing, at each time step, the virtual increase in value of the greenhouse system (including stored heat). As long as the heat buffer is neither empty nor full, the virtual value (co-state) of the stored heat remains constant. When the buffer is full (towards the end of a day), this value is gradually decreased, until the buffer starts to discharge. When the buffer empties (towards the end of a night), the virtual value is gradually increased, until recharging of the buffer starts again. This heuristic strategy is meant to minimize the time that the buffer is empty or full, because in these states the buffer is inactive (ineffective). Simulations with an annual weather sequence show the following: (1) the winter-Time virtual value of stored heat is about equal to the actual cost of heat, while in summer it is close to zero; (2) the utilization of the buffer, judged by the time on the storage bounds (full or empty), is roughly uniform along the year; (3) the performance of the system improves asymptotically with an increase of the installed capacity of the buffer; (4) expensive energy (heat) results in reduced intensity of cultivation (less heat and less yield).
Original languageEnglish
Title of host publication5th International Symposium on Models for Plant Growth, Environment Control and Farming Management in Protected Cultivation, HortiModel 2016
PublisherInternational Society for Horticultural Science
Pages119-127
Volume1182
ISBN (Electronic)9789462611788
DOIs
Publication statusPublished - 25 Nov 2017

Publication series

NameActa Horticulturae
Volume1182
ISSN (Print)0567-7572

    Fingerprint

Keywords

  • Co-state-based policy
  • Co2 enrichment
  • Day-To-night heat storage
  • Greenhouses

Cite this

Seginer, I., Van Straten, G., & Van Beveren, P. J. M. (2017). Day-To-night heat storage in greenhouses: A simulation study. In 5th International Symposium on Models for Plant Growth, Environment Control and Farming Management in Protected Cultivation, HortiModel 2016 (Vol. 1182, pp. 119-127). (Acta Horticulturae; Vol. 1182). International Society for Horticultural Science. https://doi.org/10.17660/ActaHortic.2017.1182.14